![]() ![]() Remember that the Net-ENI has only a small number of TCP connections it can handle two incoming, two outgoing, and two either way. ![]() You need to have configured the IP address of the target device equivalent to DF1 Node 0 in the Net-ENI utility or by using a configuration message inside the SLC-5/03.Ĭonfiguring the DF1:IP table is described in the 1761-UM006 user manual for the 1761-NET-ENI on page 4-6 and in Chapter 5.ģ. Sending an outgoing message via a 1761-NET-ENI requires you to use the DF1 Address : IP Address table inside the Net-ENI. I typically do not use the same data file for my Control Blocks as for the actual data payloads, and I use separate data files for data I'm transmitting and data I expect to receive.Ģ. Your actual data payload must use different memory addresses. If you are planning to use N7:0 as the start of your Control Block, you need to reserve N7:0 through N7:13. The Control Block for a MSG instruction that uses the SLC-5/03 serial port is 14 Words long. ![]() This is an intermediate difficulty programming challenge. ![]()